To Cite or Not to Cite – Evaluating Installation in NFPA 25

Conducting an evaluation of a sprinkler system design or installation is outside the scope of NFPA 25, The Standard for Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems. In this blog we will explore what NFPA 25 says about testing of components and devices through the owner’s evaluation section (4.6.1).When a main drain test cannot be conducted because the drain will not handle the full flow, does this qualify as an installation issue or can it be cited on an inspection and testing report? It is commonly not cited because it was approved or accepted by an Authority Having Jurisdiction (AHJ). Does this mean it shouldn’t be cited? This question is also the same for testing flow switches when there is not a proper inspector’s test connection.  

Read More

Does NFPA 25 Cover Limited Area Sprinkler Systems?

Does NFPA 25, the Standard for Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems encompass limited sprinkler systems?  This is a common question throughout the ITM community.  First, let us define the components that make up a sprinkler system.  In simple terms, it is a piping network with sprinklers that must have a water supply, water control valve, water flow alarm device and a drain. 

Read More

The Basics of NFPA 25 Record Keeping

Most fire sprinkler contractors will retain fire sprinkler inspection, testing, and maintenance reports (ITM), but what does NFPA 25, The Standard for Inspection Testing and Maintenance of Water-Based Fire Protection Systems, require? 

Read More

Chapter 6 Standpipe and Hose Systems. NFPA 25 ITM series

Standpipe systems are just as important as any other fire protection systems in a building. They are not only important for firefighters, but they are also imperative for firefighters to be able to safely ensure occupants are out of the building, and for extinguishing a fire. In many cases the standpipe systems are overlooked as an integral part of fire protection. For them to be fully operational, they must be properly maintained in accordance with Chapter 6 of NFPA 25, The Standard for Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems.

Read More